VE.Bus Error 24 — Victron
Switch-over system protection initiated
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)
Meaning
Current was detected flowing through the back-feed relay while it should be open, so the system stopped switching to grid/generator.
Likely causes
- External current sensor connected but option not checked in VEConfigure
- Too much AC load at switch-over preventing relay opening
- Generator AC voltage dropping slowly before rejection
- Faulty back-feed relay or current measurement circuit
Checks
- Check 'External current sensor connected' in VEConfigure if an external sensor is used
- Remove excessive load at switch-over
- Raise the lower AC input voltage limit (e.g. 210 VAC) for generators
- Replace faulty unit if a relay/measurement fault is confirmed
Safety flags
- dc_bus
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- back-feed relay
- AC loads
Citations
https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes
type: vendor_kb · retrieved: 2026-11-21 · locator: § Error 24 - Switch-over system protection initiated
This error indicates that one or more units report feeding back a significant current through its back-feed relay, while those relay are supposed to be open, and -obviously- no current can flow through an open circuit.