VE.Bus Error 11 — Victron
Relay test fault (installation or relay failure)
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)
Meaning
A failed automatic self-test of the MultiPlus-II / EasySolar-II relays; usually an installation or wiring issue, but can be a hardware failure.
Likely causes
- Earth not grounded per local grid rules, or Earth connected to Neutral in the unit
- AC-in Line/Neutral inverted
- Leakage between load, neutral and ground
- Faulty relay
Checks
- Update firmware to latest
- Verify the earth connection and that Earth is not connected to Neutral in the unit
- Isolate AC-out (disconnect L and N) and test
- Check the Neutral-out / Neutral-in connection per grid code
- Check Line/Neutral are not swapped
Safety flags
- dc_bus
- grid_tie
- pv_dc
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- relay
- AC wiring
- earthing
Citations
https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes
type: vendor_kb · retrieved: 2026-11-21 · locator: § Error 11 - Relay Test Fault - Installation error or possibly relay failure
Error 11 indicates a failed automatic self-test of the MultiPlus-II or EasySolar-II relays.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.