VE.Bus Error 1 — Victron
Device switched off because another phase switched off
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)
Meaning
In a multi-phase system one phase has failed (commonly low battery, overload, or high temperature), so the other phases report Error 1 and switch off.
Likely causes
- Low battery, overload, or high temperature on one phase
Checks
- Find the failing phase (the one NOT showing Error 1) and read its LEDs for overload / low battery / temperature
- Check the alarm log on the GX device or VRM while the fault is present
Safety flags
- dc_bus
- grid_tie
- lithium_battery
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- battery
- AC loads
Citations
https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes
type: vendor_kb · retrieved: 2026-11-21 · locator: § Error 1 - Device is switched off because one of the other phases in the system has switched off
One of the phases in a multi-phase system has failed.