2x2C — SolarEdge
No country selected
severity: stopconfidence: verifiedkind: error1 citation(s)
Scope: SolarEdge single-phase and three-phase inverters (Europe & APAC)
Meaning
No country/grid code has been selected in the inverter, so it cannot apply the correct grid limits. The addendum says to select the country as described in the Country and Grid section of the installation guide.
Likely causes
- Country not set during commissioning
- Firmware update or board replacement cleared the setting
Checks
- Select the country in SetApp as described in the installation guide's Country and Grid section
- Re-commission the inverter and confirm it connects
Safety flags
- grid_tie
Citations
type: manual · retrieved: 2026-11-21 · locator: p. 4
No Country Selected Select the country, as described in the Country and Grid section of the installation guide.