2x19 — SolarEdge
Isolation fault
severity: stopconfidence: verifiedkind: error1 citation(s)
Scope: SolarEdge single-phase and three-phase inverters (Europe & APAC)
Meaning
The inverter detected that the PV array is not properly isolated from earth. The addendum says to check the PV installation for isolation problems and ground leakage, and that only a certified PV installer may fix the faulty string before it is reconnected.
Likely causes
- Damaged module insulation or backsheet
- Damaged DC cable, connector or junction
- Water ingress or soiling creating a path to earth
Checks
- Check the PV installation for isolation problems and ground leakage
- Use the inverter's isolation status screen (R Iso) to find the leaking string
- Leave the faulty string disconnected until a certified PV installer repairs it
Safety flags
- dc_arc
- pv_dc
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- PV modules
- DC cabling
- power optimizers
Citations
type: manual · retrieved: 2026-11-21 · locator: p. 3
Isolation Fault PV solar array is not properly isolated from ground earth.