18x7F — SolarEdge
IRCDMax (RCD current surge)
severity: stopconfidence: verifiedkind: error1 citation(s)
Scope: SolarEdge single-phase and three-phase inverters (Europe & APAC)
Meaning
The inverter detected an RCD current surge caused by insufficient insulation to ground. The addendum repeats the isolation-fault procedure: switch off, wait five minutes, disconnect AC and DC, then reconnect strings one at a time to find the faulty string, which only a certified installer may fix.
Likely causes
- Insufficient insulation to ground in the PV array
- Damaged DC cable, connector or module
- Water ingress causing leakage to earth
Checks
- Turn the inverter ON/OFF switch OFF and wait five minutes for the capacitors to discharge
- Disconnect the AC breaker and the DC inputs
- Reconnect each DC string separately until the error reappears
- Do not reconnect a grounded string; a certified installer must repair it
Safety flags
- dc_arc
- pv_dc
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- PV modules
- DC cabling
- RCD
Citations
type: manual · retrieved: 2026-11-21 · locator: p. 6
IRCDMax RCD current surge.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.