18x37 — SolarEdge
V-Line max (line-to-line over-voltage)
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: SolarEdge single-phase and three-phase inverters (Europe & APAC)
Meaning
The line-to-line AC voltage exceeded the country limit. The addendum says to verify the country setting, switch the site's inverters off and verify the AC grid voltage, use a larger gauge AC wire on long runs, consult the grid operator and, where permitted, change the grid protection values.
Likely causes
- Grid over-voltage above the country limit
- Wrong country/grid-code setting
- Voltage rise on a long or undersized AC run
Checks
- Verify the inverter is set to the correct country
- Turn off the site's inverters and measure the AC grid voltage
- Use a larger gauge AC wire if the run to the grid connection point is long
- Consult the grid operator and change grid protection values only where permitted
Safety flags
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- AC wiring
Citations
type: manual · retrieved: 2026-11-21 · locator: p. 5
V-Line Max AC voltage too high Verify that the inverter is set to the correct country.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.