401 — SMA
Grid incident - stand-alone grid or large frequency change
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
Meaning
Events 401 and 404 mean the inverter has disconnected from the utility grid because it detected a stand-alone (island) grid or a very large change in grid frequency. SMA asks the installer to establish that there is no power outage or work on the utility grid, to contact the grid operator if necessary, and to check the grid connection for significant short-term frequency fluctuations.
Likely causes
- Utility grid outage or planned work on the grid
- Islanding / stand-alone grid condition at the site
- Large step change in grid frequency
Checks
- Make sure there is no power outage or work being done on the utility grid and contact the grid operator if necessary
- Check the grid connection for significant short-term frequency fluctuations
Safety flags
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- grid connection
Citations
https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 85
Explanation: The inverter has disconnected from the utility grid. A stand-alone grid or a very large change in the grid frequency was detected.