3901 — SMA
Waiting for DC start conditions - start conditions not met
severity: warningconfidence: verifiedkind: error1 citation(s)
Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
Meaning
Events 3901 and 3902 are a wait state, not a fault: the feed-in conditions for the utility grid are not yet fulfilled, so the inverter has not started. SMA's measures are to clear snow or shade from the array, wait for higher irradiation and, if it happens every morning, raise the parameter 'Critical voltage to start feed-in'.
Likely causes
- Low irradiation in the morning or poor weather
- Snow cover or shading on the PV array
- Start voltage parameter set too high for the array
Checks
- Ensure that the PV array is not covered by snow or otherwise shaded
- Wait for higher irradiation
- If the message appears frequently in the morning, increase the parameter Critical voltage to start feed-in
Safety flags
- pv_dc
Parts
- PV modules
Citations
https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 91
Explanation: The feed-in conditions for the utility grid are not yet fulfilled.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.