3701 — SMA
Residual current too high - check generator
severity: stopconfidence: verifiedkind: error1 citation(s)
Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
Meaning
The inverter has detected a residual current caused by the brief grounding of the PV module, which points at an insulation fault on the array. SMA's measure is to check the PV system for ground faults.
Likely causes
- Insulation fault to earth in the PV array
- Damaged DC cable or connector
- Moisture path from the array to earth
Checks
- Check the PV system for ground faults
- Isolate strings one at a time to locate the leaking string
- Have the faulty string repaired before it is reconnected
Safety flags
- dc_arc
- pv_dc
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- PV modules
- DC cabling
- RCD
Citations
https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 90
Explanation: The inverter has detected a residual current through brief grounding of the PV module.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.