3501 — SMA

Insulation failure - check generator

severity: stopconfidence: verifiedkind: error1 citation(s)

Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)

Meaning

The inverter has detected a ground fault in the PV module, meaning the insulation from the array to earth is defective or insufficient. SMA's measure is to check the PV system for ground faults before the array is returned to service; the manual's dedicated section 11.3 covers the procedure and warns of lethal shock risk from parts that stay live during a ground fault.

Likely causes

Checks

Safety flags

Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.

Parts

Citations

https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf

type: manual · retrieved: 2026-11-21 · locator: p. 89

Explanation: The inverter has detected a ground fault in the PV module.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.