3501 — SMA
Insulation failure - check generator
severity: stopconfidence: verifiedkind: error1 citation(s)
Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
Meaning
The inverter has detected a ground fault in the PV module, meaning the insulation from the array to earth is defective or insufficient. SMA's measure is to check the PV system for ground faults before the array is returned to service; the manual's dedicated section 11.3 covers the procedure and warns of lethal shock risk from parts that stay live during a ground fault.
Likely causes
- Damaged module insulation or backsheet
- Damaged DC cable, connector or junction box
- Water ingress or soiling forming a leakage path to earth
Checks
- Disconnect the product from voltage sources and ensure it cannot be reconnected
- Check the PV system for ground faults, string by string, with an insulation tester
- Do not reconnect a faulty string until it has been repaired
Safety flags
- dc_arc
- pv_dc
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- PV modules
- DC cabling
Citations
https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 89
Explanation: The inverter has detected a ground fault in the PV module.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.