Grid incident - ten-minute average grid voltage exceeded
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
Meaning
The ten-minute average value of the grid voltage has left the permissible range because the grid voltage or grid impedance at the connection point is too high, so the inverter disconnects from the utility grid to maintain power quality. SMA's remedy is to verify the grid voltage during feed-in and to have the grid operator adjust the feed-in voltage or the monitored limits.
Likely causes
- Sustained grid over-voltage over the ten-minute averaging window
- High grid impedance at the connection point
Checks
- During feed-in, check whether the grid voltage at the connection point is permanently within the permissible range
- If local grid conditions are the cause, ask the grid operator to adjust the feed-in voltage or the monitored operating limits
- If the voltage is in range and the message persists, contact SMA Service
Safety flags
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- grid connection
Citations
https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 84
Explanation: The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.