1501 — SMA
Reconnection fault grid
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
Meaning
The changed country standard, or the value of a parameter that was set, does not correspond to the local requirements, so the inverter cannot connect to the utility grid. SMA's remedy is to select the parameter 'Set country standard' and check its value.
Likely causes
- Country standard not matching the site's grid code
- A grid parameter set outside the local requirements
Checks
- Select the parameter Set country standard and check its value
- Correct the country standard to match the local grid requirements
- Re-commission and confirm the inverter connects to the grid
Safety flags
- grid_tie
Parts
- grid connection
Citations
https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 88
Explanation: The changed country standard or the value of a parameter you have set does not correspond to the local requirements. The inverter cannot connect to the utility grid.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.