1101 — SMA
Installation fault - check connection
severity: stopconfidence: verifiedkind: error1 citation(s)
Scope: SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
Meaning
A second line conductor has been connected to the neutral terminal N. The manual's corrective measure is to connect the neutral conductor to N, which means correcting the AC terminal wiring at the inverter.
Likely causes
- Two line conductors landed on N
- AC terminal wiring error at installation
Checks
- Isolate the AC supply and prove dead
- Connect the neutral conductor to N
- Re-check the terminal assignment before re-energising
Safety flags
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- AC wiring
- AC terminal
Citations
https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 88
Explanation: A second line conductor is connected to N.