60 — Growatt

Negative power fault

severity: degradedconfidence: verifiedkind: error1 citation(s)

Scope: Growatt SPF 3500/5000 ES off-grid solar inverter

Meaning

A negative power condition, typically a parallel-system wiring or configuration problem.

Likely causes

Checks

Safety flags

Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.

Parts

Citations

https://en.growatt.com/upload/file/SPF_3500-5000_ES_User_Manual_EN_202109.pdf

type: manual · retrieved: 2026-11-21 · locator: p. 40

Negative power fault. — Check whether the AC output connected to the grid input. Check whether Program 8 settings are the same for all parallel inverters. Check whether the current sharing cables are connected well in the same parallel phases. Check whether all neutral wires of all parallel units are connected together.
Independent and unofficial. Verify against the manual for your exact model and serial number before acting. See this code on the owning surface: SolarDesk.