Negative power fault
severity: degradedconfidence: verifiedkind: error1 citation(s)
Scope: Growatt SPF 3500/5000 ES off-grid solar inverter
Meaning
A negative power condition, typically a parallel-system wiring or configuration problem.
Likely causes
- AC output connected to the grid input
- Mismatched program 8 settings across parallel inverters
- Poor current-sharing cable or neutral connections
Checks
- Check the AC output is not connected to the grid input
- Check program 8 settings match on all parallel inverters
- Check current-sharing cables and that all neutral wires of parallel units are connected together
Safety flags
- grid_tie
Requires a qualified installer. Isolate and escalate to a qualified installer/electrician.
Parts
- AC wiring
- parallel cabling
Citations
https://en.growatt.com/upload/file/SPF_3500-5000_ES_User_Manual_EN_202109.pdf
type: manual · retrieved: 2026-11-21 · locator: p. 40
Negative power fault. — Check whether the AC output connected to the grid input. Check whether Program 8 settings are the same for all parallel inverters. Check whether the current sharing cables are connected well in the same parallel phases. Check whether all neutral wires of all parallel units are connected together.